Gold Member Since 2007
Audited Supplier
Xinchi Electric Co., Ltd.

Circuit Breaker 1p+N, 1p+N RCBO, 4.5ka Circuit Breaker manufacturer / supplier in China, offering 4.5ka Australia Miniature Circuit Breaker 1p+N RCBO, Suntree Hot Sale Solar Inverter 10000 Watts for Solar System, 4p 1200V PV Solar System DC Isolator Switch and so on.

(/ )

Supplier Homepage Product AC MCB 4.5ka Australia Miniature Circuit Breaker 1p+N RCBO

4.5ka Australia Miniature Circuit Breaker 1p+N RCBO

FOB Price: US $5.9 / Piece
Min. Order: 1 Piece
Min. Order FOB Price
1 Piece US $5.9/ Piece
Get Latest Price
Production Capacity: 10000PCS/Week
Transport Package: Standard
Payment Terms: L/C, T/T, Paypal

Request a custom order and have something just for you!

Send Customized Request
Basic Info
  • Model NO.: DRNL
  • Operation: Manual Type
  • Arc-extinguishing Medium: Air
  • Structure: Conventional Circuit Breaker
  • Type: Circuit Breaker
  • Certification: ISO9001-2000, CE, CB, SAA
  • Quality Assurance: Two Years
  • Magnetic Tripping Characteristics: 6 10 16 20 25 32A
  • Rated Voltage Ue: 240VAC
  • Pollution Degree: IP22
  • Trademark: suntree/oem
  • Origin: Zhejiang
  • Breaking Capacity: Low Voltage Circuit Breakers
  • Speed: Normal Type Circuit Breaker
  • Installation: Fixed
  • Poles Number: 1p+N
  • Function: RCCB
  • Certificate: CB, Nemko, TUV, CE, SAA
  • Brand: Suntree/OEM
  • Rated Current(a): 6ka 4.5ka
  • Rated Frequency: 50Hz/60Hz
  • Product: 1p+N RCBO
  • Specification: CE SAA TUV
  • HS Code: 8536620000
Product Description
4.5KA Australia Miniature Circuit Breaker 1P+N
Technical DataDRNL
StandardsAS/NZS 61009 - 1
Magnetic tripping characteristicsB,C
Residual tripping characteristicsA , AC
Rated current(A)6, 10, 16, 25, 32
Rated residual current10mA, 30 mA, 100mA
Calibration temperature30°C
Rated voltage 1P240V
Frequency50/60
Maximum service voltage264
Tripping Duration:Instaneous<0.1s
Power supplyTop or bottom
Selectivity class3
Residual making and breaking capacity2000A
Short circuit capacity6000A/4500A
Isolation application (IEC 60947-2)Yes
Insulation resistance (Mohm)1,000
Insulation voltage (V)500
Dielectric rigidity (V)2,500
Vibration resistance1.5g
Endurance (operations) electrical>6,000
mechanical>20,000
Protection degree outsideIP20
inside enclosureIP40
Self extinguishing degree (UL 94)V2
Tropicalisation (IEC 60068-2)+55°C/95% RH
Operating temperature-5/+55°C
Storage temperature-25/+70°C
Terminal capacity (top & bottom) min / max1-16mm
Terminal torque (top / bottom)3
Busbar systemsYes
AccessoriesNo
Dimensions (mm)72(H)81(L)18(W)
Weight (g)105


Features & Advantages:
The slimest 6kA RCBO in this world.
the newest design compared with competitors.
Genuine 6kA fault level declared after hundreds of seriously passed test.
Suit both residential and commercial applications.
Top and bottom line and load compatible newest design for ease of installation.
Two pole safety feature allows switching of both Active and Neutral contacts.
Active contacts always connect earlier and break later;
Single module is ideal to save valuable switchboard space.

Normal Operation Conditions
Ambient Air temperature:Ambient air temperature range from -5°C ~+40°C ,not exceeding 35°C averagely in 24 hours.
Location:installation location can not exceed 2000 meters above sea level.
Air conditons:Relative humidity in the installation palce can not exceed 50% when the air reaches the highest temperature +40°C ,
the average minimum temperature when it is the wettest can not exceed 25°C Relative humidity not exceeding 90%.
Installation conditions:Magnetic field outsid the installation place can not exceed 5 times of the site of terrestrial magnetism in all
directions.Normally speaking,RCBO should be mounted vertically .If the operation handle puts through power source upward,there should
be no notable impact and vibration in the installation place.
LeakAge protection function of RCBO is tested and adjusted by the manufacture,users can not open the products at random during usage.
After using RCBO for a certain time(normally one month) , test button should be pressed noce in a state of making the circuit to check
whether the function of RCBO is normal and reliable(press test button once, the RCBO can break off noce) . If abnormal, it should be
unloaded and sent to the manufacturer to repair.
RCBO can not be wetted or soaked by rain,snow or water during the course or transportation storage and usage.
Send your message to this supplier
Avatar
Miss Sary
Sales Manager
*From:
To: Miss Sary
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

Find Similar Products By Category